FMM-7045, FMM-7045-D
Installation Instructions
Multiplex Addressable
Manual Pull Stations
EN
FMM-7045, FMM-7045-D | Installation Instructions | 3.0Specifications
.
2.3
Wiring
2.4
Mounting
Make sure all power is removed before
making any electrical connections. Failure
to do so may result in personal injury and/or
damage to equipment.
The FMM-7045/FMM-7045-D mounts to a 3 in. x 2 in.
x 3½ in. device box (like a Steel City CXW) or a 4 in.
x 2 1/8 in. square box with a 5/8 in. mud ring (like the
Steel City 52171 box and 52-C-14-5/8 mud ring) with
the two provided screws. The multiplex single zone
input module should easily fit inside.
Run all wires and make all connections before
mounting the FMM-7045/FMM-7045-D. All wiring is
supervised and power limited. See Figure 2 for details.
The back plate mounting holes on the FMM-
7045/FMM-7045-D can be accessed by opening the
key lock on the unit.
Do not loop wire around each terminal.
Break terminal wire connections for
supervision.
The FMM-7045/FMM-7045-D Pull Stations
are for indoor use only. If a pull station is
needed for outdoor use or in an unheated
area, an FMM-100 Series Pull Station rated
for the environment should be wired to a
multiplex module within the interior of the
building.
Figure 2: Wiring the FMM-7045
2
2
4
1
3
3
3.0 Specifications
Table 1: Specifications
L
o
o
p
L
o
o
p
+
-
HUNDREDS
0
1
2
0
1
2
X X X
Panel
Programming
Type
Single Point
0
5
0
1
9
1
9
8
7
2
3
8
7
2
3
6
4
6
4
5
ONES
TENS
Control Panel
Requirements
D7024 or DS9400 Series FACP (with
ROM version 2.0 or greater and a
D7039 or DS9431 Multiplex Expansion
Module installed). Refer to the D7024
Operation and Installation Guide (P/N:
31499) or the DS9400M/DS9400i
Installation Guide (P/N: 44578) for
specific programming information. Refer
to the D7039 Installation Instructions
(P/N: 38685) or the DS9431
1 - Previous device or D7039/DS9431
2 - Loop (+)
3 - Loop (-)
Installation Instructions
41831) for multiplex wiring information.
(P/N:
4 - Other devices
Multiplex Bus
Average Current
Draw
Alarm: 0.55 mA
Standby: 0.55 mA
Optional
Equipment
Replacement Glass Break Rods (FMM-
100GR)
Operating
Temperature
+32°F to +120°F (0°C to +49°C) non-
condensing RH
Listings and
Approvals
UL864
CSFM
Nominal Bus
Voltage
12 VDC
Bosch Security Systems, Inc. | 8/06 | F01U001402C
3
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450-9199
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189
© 2006 Bosch Security Systems, Inc.
F01U001402C
|
Best Ventilation Hood ISER222 SERIES User Manual
Black Box Portable Generator BLACK BOX Pattern GeneratorVGA User Manual
Bosch Power Tools Planer PLH181B User Manual
Bravetti Food Processor BP101H2 User Manual
BRK electronic Fire Extinguisher BF5 User Manual
Brother Sewing Machine BE 0901E User Manual
Cambridge Audio Stereo Receiver 840A V2 User Manual
Cannon Double Oven 10101G User Manual
CFM Fan 165834 User Manual
Chauvet Welder F 40 User Manual